Home > Products > Transformer Test > Short Circuit Test > Load Test of Transformer
Load Test of Transformer
  • Load Test of TransformerLoad Test of Transformer

Load Test of Transformer

Load Test of Transformer,Weshine® Transformer LV Short-circuit Impedance Tester is not provided with an external voltage regulator and adopts the primary connection mode. It begins the three-phase testing and calculates impedance error percentage automatically when the parameter is entered and provides intuitive results. This is a rapid tester which detects winding deformation of transformers on site.

Send Inquiry    PDF DownLoad

Product Description

Weshine® Transformer LV Short-circuit Impedance Testerfor Load Test of Transformer


The automatic transformer low-voltage short-circuit impedance tester has two test power models:

1. Internal power supply: The three-phase transformer test can be completed with one wiring without an external voltage regulator. The test is simple and suitable for on-site testing.

2. External power supply: apply test power through a voltage regulator, suitable for indoor testing.        


Display three-phase voltage, three-phase current, three-phase power, three-phase short-circuit impedance (Zk), three-phase short-circuit reactance (Xk), three-phase short-circuit inductance (Lk), three-phase short-circuit impedance voltage (Zke), and automatically calculate the transformer Converted to rated temperature, rated current in percent impedance voltage, and percent error from nameplate impedance. It can be used to check the single-phase defects of three-phase transformers.


Weshine® Load Test of Transformer can record the data of three single-phase measurements, and can calculate the impedance voltage and impedance voltage percentage error of the transformer according to the different connections of the transformer. After three single-phase tests are completed, the calculation results of three-phase short-circuit impedance can be displayed. The test results are automatically converted, with frequency correction, temperature conversion, and current conversion to improve the comparability of test data. VS-6309B has no-load and load test functions.


Weshine® Load Test of Transformer Parameter (Specification)


PRODUCT INFORMATION

Product Name

TRANSFORMER SHORT CIRCUIT IMPEDANCE TESTER

Voltage Range

15 V ~ 500V

Current Range

0.5 A ~ 50 A

Functions

Short circuit impedance test, Zero sequence impedance test, load test, no-load test

Typical Application

High voltage power transformers.

Weight

9.5 kg

Certificates

CE; EMC; LVD; ISO; IEC;

Dimensions

405mm*330mm*180mm

Model Number

VS-6309 Series


Load Test of Transformer Features


1. Single-phase impedance, three-phase impedance, zero-sequence impedance (star with neutral point) measurement, no-load test function.

2. Two power supply modes: internal power supply and external single-phase voltage regulator.

3. The voltage and current test range is wide and the precision is high.

4. With a 7.0-inch touch screen, the operation is simple.

5. Built-in large-capacity memory, not easy to lose, can save 160 sets of data.

6. Built-in high-speed micro thermal printer, which can print test data.

7. Built-in high-precision clock, real-time display time.

8. With U disk storage function.


Quality Certificates


We always believe that all the success of our company is directly related to the quality of the products we provide. Open Circuit Test of Transformer meet the highest quality requirements specified in ISO9001, ISO14000:14001 guidelines and our strict quality control system.



Shipment 


For further information on Weshine's Service Solutions, contact our 24/7 online sales representative to get quotes from Weshine.


Contact us


FEEL FREE TO MAKE A PHONE CALL:400 996 1868

OR E-MAIL TO: info@weishengelectric.com

SALES OFFICE

Weshine Limited 602, Building 3, Diangu

Technology Center, No. 3088, Lekai North Street

W/app: +86 1873 1260 588

E. info@weishengelectric.com

sale01@weishengelectric.com


CONTACT OFFICE

T. 0312 3188565

E. bdweisheng@weishengelectric.com


AFTER-SALES SERVICE

T. +86 157 1252 6062


Hot Tags: Load Test of Transformer, Buy, China, Manufacturers, Suppliers, Factory, Price, Purpose, Specification, Results, Definition
Related Category
Send Inquiry
Please feel free to give your inquiry in the form below. We will reply you in 24 hours.
X
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept